Home / Inverter sizing / Clinic reception

550W average load - 5 hour target - 24V system

What size inverter and battery does a clinic reception need?

For a clinic reception running 550W average load for 5 hours, Battery Buddy sizes a 900VA inverter and a 220Ah battery bank at 24V — 2 x 220Ah 12V batteries in series. The energy target is 2750Wh, which needs 327Ah at 70% efficiency and 50% depth of discharge. Charge it at 22-27A.

The load this premises actually carries

Waiting-room comfort, reception computer and continuous CCTV coverage. Each appliance is counted at the minutes it genuinely runs in an hour, not at full nameplate wattage for sixty minutes — that duty-cycle step is what separates a sizing you can trust from a dealer's round number.

Average hourly load, appliance by appliance
ApplianceWatts eachQtyMinutes per hourAverage draw
Ceiling Fan70W360 min210W
LED Tube Light20W460 min80W
Desktop Computer200W160 min200W
CCTV + DVR60W160 min60W
Total average hourly load550W

Why 900VA and not something bigger

Inverters are sold in VA, not watts. Battery Buddy converts with the standard power factor of 0.8 and adds a 25% safety margin: (550W / 0.8) x 1.25 = 859VA, which rounds up to the 900VA tier actually sold in Indian retail.

Oversizing is not free. A larger inverter idles at a higher no-load draw, costs more, and tempts you to add load the battery cannot support. Size the inverter to the load, then size the battery to the outage.

Why the system runs at 24V

Medium loads with improved efficiency. Typically two 12V batteries in series. Battery Buddy escalates system voltage automatically once average load passes 400W (to 24V), 800W (to 48V) and 2000W (to 96V). At 550W this profile sits at 24V.

Higher DC voltage carries the same power at lower current, which means less heat in the cabling and a safer install. The cost is that batteries must be added in matched series sets — 2 x 220Ah 12V batteries in series.

Battery bank and charging

Target energy is 550W x 5 hours = 2750Wh. Dividing by 24V x 0.7 efficiency x 0.5 depth of discharge gives 327Ah, and the nearest standard bank is 220Ah — rated for a sustained load of 560-750W.

Charge it at 22-27A, the C/10 to C/8 guideline. Under-charging leaves a lead-acid bank permanently short of full and is one of the most common reasons backup quietly halves over two years.

Note: at this bank size the honest achievable runtime on this load is about 3 hours 22 minutes, short of the 5-hour target. Either add a parallel string, move to the next voltage tier, or accept a shorter window and plan what you switch off.

The overload check nobody runs

With everything on, continuous draw is 550W. The Ceiling Fan spikes to about 315W at start-up, so peak demand is 865W. A 900VA inverter holds that with 4% headroom.

Backup target versus battery cost

Every extra hour of backup is bought with amp-hours. This is the trade-off for exactly this load.

What each backup target costs you in battery
Backup targetEnergy neededBank Ah requiredNearest retail bank
2 hours1100Wh131Ah150Ah at 24V
3 hours1650Wh196Ah200Ah at 24V
4 hours2200Wh262Ah220Ah at 24V
5 hours2750Wh327Ah220Ah at 24V
6 hours3300Wh393Ah220Ah at 24V
8 hours4400Wh524Ah220Ah at 24V

Frequently asked questions

What size inverter is needed for a clinic reception?

A 900VA inverter for a 550W average load. That comes from (550 / 0.8) x 1.25 = 859VA, rounded up to the nearest standard retail size.

What battery capacity does a clinic reception need for 5 hours of backup?

About 327Ah at 24V, which maps to a standard 220Ah bank — 2 x 220Ah 12V batteries in series. The energy target is 2750Wh at 70% efficiency and 50% depth of discharge.

Should this run on 12V or a higher system voltage?

24V. Medium loads with improved efficiency. Typically two 12V batteries in series. The threshold Battery Buddy uses is 400W average load for 24V, 800W for 48V and 2000W for 96V.

What charging current should the inverter provide?

22-27A, following the C/10 to C/8 guideline for a 220Ah lead-acid bank. Too little current never completes a cycle in short grid windows; too much cooks the electrolyte.

Will the inverter trip when a motor starts?

Peak demand here is 865W — 550W continuous plus the 315W start-up surge of the Ceiling Fan. A 900VA inverter clears it.

Is this a brand recommendation?

No. Battery Buddy is brand-neutral and free — it returns a VA rating, an Ah figure, a system voltage and a charger current, and shows the formula behind each. Take those four numbers to any dealer and compare quotes on equal terms.

Battery Buddy is free, needs no sign-up, sells no batteries and shows every formula it uses. It is built by Flocci Technologies, an India-first AI-native software studio behind 30+ apps that share one Flocci identity.